Guidelines for integrated territorial planning – Heat pump
“Smart house” is energetically
provided with renewable energy sources. Solar energy is exploited also with
greater solar collector’s installation for water preparation that heats facilities
and other water requirements. Water is at lower temperatures in reservoir heated
with heat pump, at peak time and by increased use with district wood biomass heating.
So as an additional secondary heating system we use heat pump type water-water.
Brand of the heat pump is Termotechnik model VV 13/15 E1. As a heat source is
used underground water trough pumping it within the evaporator of the heat pump
using submersible pump. In the evaporator underground water transmits heat and
cooled water for proximately 3 to 4
°C
returns back. The heat pump achieves very high level
of efficiency. Before purchasing and installation is necessary to check the
availability of underground water and the temperature of the water. Temperature
of the underground water can not be lower then 7 °C
(in our case the
temperature of underground water is 14 °C), required is minimum flow of 0, 2 m³/h
for 1 kW of heat power (in our case, the flow is 3, 4 m³/h). Due to the higher
heating number are recommended low-temperature heating systems in our case the
heating is in walls and floor.
Next to the heating is also carried out passive cooling system of the facility. For cooling we have a system by which the cold source (ground water) is pumped trough an intermediate heat exchanger, which cools water for cooling facilities. Cooling of facilities is carried out with help of floor and wall piping system. Such system is effectively reduced, because we can not allowed temperature water in piping system to go below + 18 ° C to avoid condensation of floor and wall surface. For calm cooling trough walls and floors are available two passive cooling stations PA SIV 6 R and PA SIV 10 R, which prevents the cooling water to drop temperature below the dew point.
Heat pump has a simple control management TERMOTRONIC 3000:Indication for the Bio-construction Action Plan
Possible criteria for MED bio-housing quality certificate
− Bistra hiša - Smart house (Martjanci, Slovenia)